SIGNAL INPUT | 4 ~ 20mA standard current signal or voltage signal |
---|---|
AMOUNT PROCESS | Set according to the detection range of the connected gas detector |
ACCURACY | ≤± 3% F.S |
RESPONSE TIME | ≤5S |
DISPLAY MODE | LCD displays gas concentration and operation information, and LED light indicates working status |
ALARM MODE | Two-stage sound and light alarm, sound ≥ 85dB@30cm |
ALARM SETTING | The low section alarm point can be set arbitrarily, and the high section is fixed |
OUTPUT POWER SUPPLY | Each circuit provides 24VDC 200mA |
DETECTOR WIRING | Three wire system |
---|---|
OUTPUT SIGNAL | two sections of passive switching value output, contact capacity 1A 24VDC Either-or: 4 ~ 20mA standard current signal Modbus / RS 485 communication interface |
STANDBY POWER SUPPLY | 24VDC rechargeable battery (optional) |
WORKING POWER SUPPLY: | 220VAC 50Hz |
POWER CONSUMPTION | ≤ 2W / circuit |
RELATIVE HUMIDITY | 0~ 99% RH / no condensation |
TEMPERATURE RANGE | -20℃~+60℃ |
CABINET TYPE | Panel mounted, wall mounted, cabinet type |